Installer tools · DC cable

DC cable calculator

Two minima, calculated independently — current-carrying capacity after correction, and the CSA needed to hold your volt-drop criterion — then the larger standard size, and which constraint set it.

The circuit

A
Work it out from module Isc
A

Isc MAX = strings × Isc(STC) × 1.25, the 1.25 accounting for irradiance above STC (IET, April 2026).

V

What the volt drop is expressed as a percentage of.

m

Both legs are counted — 2 conductors in the path.

The string pair: positive and negative run together against a surface. This is a rated arrangement, so the pair's mutual heating is already in the figure — adding a grouping factor for those same two cables would derate them twice.

Volt-drop criterion
%

Common DC design practice for PV string circuits. Not a regulatory limit, and this tool does not present it as one.

Conditions, grouping and cable type
°C

Rating basis is 60 °C. Values below it get a factor of 1.00 — the table offers no uplift.

The selected arrangement already rates 2 loaded cables together. Apply a factor only for circuits beyond that pair.

Grouping factors for larger groups come from tables this tool is not licensed to reproduce. Enter the factor you are designing to and name its table — it is recorded in the calculation trail alongside everything else.

Anything else you are derating for. 1.00 = none.

°C

Defaults to the cable's maximum continuous conductor temperature (90 °C) — conservative, and comparable with tabulated mV/A/m figures. Lower it if you have a realistic operating temperature.

2 for a two-wire DC circuit — positive and negative.

Recommended cable

6mm²

Voltage drop governs

Voltage drop sets the size. Current-carrying capacity alone would allow 1.5 mm². Cable range alone would allow 1.5 mm².

Tabulated capacity
57 A
After correction
57 A
Volt drop
3.63 V
as % of circuit
0.91 %

Minimum CSA · Current-carrying capacity

1.5 mm²

How this was reached
  1. Design current (Ib)14.00 A

    The current the circuit is designed to carry continuously.

  2. Installation arrangementTwo loaded cables touching, on a surface

    The string pair: positive and negative run together against a surface. This is a rated arrangement, so the pair's mutual heating is already in the figure — adding a grouping factor for those same two cables would derate them twice.

    Source: Keystone Cable, Polycab, HES Kablo

  3. Ambient correction (Ca)1.00

    60 °C against a 60 °C rating ambient — taken from the 60 °C row of the conversion table, not interpolated.

    Source: Keystone Cable, Polycab

  4. Grouping (Cg)1.00

    None applied. The "Two loaded cables touching, on a surface" rating already accounts for 2 loaded cables, so the string pair needs no further factor.

  5. Combined correction factor1.000

    Ca 1.00 × Cg 1.00

  6. Required tabulated capacity (It)14.00 A

    Ib ÷ combined factor = 14.00 ÷ 1.000. The cable must be tabulated at this or above BEFORE correction.

  7. Smallest size that carries it1.5 mm²

    Tabulated 24 A, 24.0 A after correction — against a design current of 14.00 A.

    Source: Keystone Cable, Polycab, HES Kablo

Minimum CSA · Voltage drop

Governing

6 mm²

How this was reached
  1. Volt-drop criterion1.00 %

    4.00 V at a circuit voltage of 400 V. This is the designer's chosen criterion, not a figure this tool imposes.

  2. Conductor path60.0 m

    30.0 m route × 2 conductors — volt drop is over the complete circuit path, not one leg of it.

  3. Conductor temperature assumed90 °C

    Resistance corrected from 20 °C by a factor of 1.2751, using α₂₀ = 0.00393 /K for copper.

    Source: Material constant

  4. Smallest size within the criterion6 mm²

    3.3900 Ω/km at 20 °C → 0.2594 Ω over the whole path at 90 °C.

    Source: Keystone Cable, Polycab, HES Kablo, Prysmian, IEC

  5. Volt drop at that size3.63 V (0.91 %)

    Ib × path resistance = 14.00 A × 0.2594 Ω, against a 4.00 V criterion.

Minimum CSA · Cable range

1.5 mm²

How this was reached
  1. Smallest size in the range1.5 mm²

    BS EN 50618 PV cable (H1Z2Z2-K) is not manufactured below this. A manufacturing fact, not a regulatory minimum.

    Source: Keystone Cable, IET

  2. Standards-imposed minimum CSAnone recorded

    This pack records no standards-imposed minimum CSA. That is an absence of data, not a statement that none applies — check your licensed copy of BS 7671 and any scheme requirements.

Every size in this range, against this circuit
CSACapacity after correctionVolt dropLoss at IbMeets
1.5 mm²24 A3.67 %205.4 Wcurrent only
2.5 mm²33 A2.20 %123.1 Wcurrent only
4 mm²44 A1.36 %76.3 Wcurrent only
6 mm²recommended57 A0.91 %50.8 Wboth
10 mm²79 A0.52 %29.2 Wboth
16 mm²107 A0.33 %18.6 Wboth
25 mm²142 A0.21 %11.9 Wboth
35 mm²176 A0.15 %8.5 Wboth
50 mm²221 A0.10 %5.9 Wboth
70 mm²278 A0.07 %4.2 Wboth
95 mm²333 A0.06 %3.1 Wboth
120 mm²390 A0.04 %2.5 Wboth
150 mm²453 A0.04 %2.0 Wboth
185 mm²515 A0.03 %1.6 Wboth
240 mm²620 A0.02 %1.2 Wboth

Loss is I²R over the whole conductor path at the design current. Going one size up reduces it — comparing that saving against the extra cable cost is a design optimisation this tool does not yet do.

Assumptions, factors and data sources

Assumptions

Cable and rating basis: BS EN 50618 PV cable (H1Z2Z2-K)
Capacities tabulated at 120 °C conductor and 60 °C ambient, on the BS EN 50618 / IEC 62930 rating basis.
Conductor: copper, resistance at 20 °C from the pack
Maximum DC resistance values, corrected to 90 °C with α₂₀ = 0.00393 /K.
Circuit path: 2 conductors × 30.0 m
A two-wire DC circuit: volt drop is taken over both the positive and the negative leg.
Volt-drop criterion: 1.00 % of 400 V
Chosen by the designer. This tool does not impose a volt-drop limit.
Ambient temperature: 60 °C
Applied by stepping up to the next tabulated row. The conversion table is not interpolated.

Factors applied

Ambient temperature (Ca): 1
60 °C is at or below the 60 °C rating ambient, so the table gives 1.00 — it offers no uplift below its rating ambient.
Grouping (Cg): 1
None applied. The "Two loaded cables touching, on a surface" rating already accounts for 2 loaded cables, so the string pair needs no further factor.

Data sources

Data pack en50618-h1z2z2k v1.0.0 · engine v1

Calculated on the BS EN 50618 / IEC 62930 rating basis published in the cable datasheets cited above, cross-checked across three manufacturers. This is not a statement of BS 7671 compliance: BS 7671's own tabulated capacities and its Table 4B1 and 4C1 correction factors are not used here and are not reproduced. Verify the result against your licensed copy of BS 7671 and against the datasheet for the cable you are actually installing.